Description
ABB XT6H 800 TMA In=800A 3p F F UL Circuit Breaker, 600 VAC/VDC, 800 A, 65 kA @ 480 VAC Interrupt, 3 Poles, TMA Trip
Tmax XT7M molded case circuit breakers offers extraordinary flexibility and completeness of range to simplify system designs and reduce inventory and procurement costs. With current ratings up to 250A and a voltage rating of 600V, both alternating (AC) and direct (DC) current in the same breaker. This combined with extended breaking capacities, up to 200kA, gives SACE Tmax XT molded case circuit breakers the ability to cover a full range of applications.
Specifications
Specifications
Manufacturer Part Number XT6HU3800BFF000XXX
Manufacturer ABB
Product Series Tmax XT7M
Family Series ABB Circuit Breakers, Tmax XT7M Series
Description Xt6H 800 E.Mdip I 800 3P Iec
Poles 3
Current Rating 800 A
Max Voltage 600 VAC
Mounting Panel
100% Rated No
UL Standard 489
Approvals CSA, UL
Gross Weight 21.22 lbs
Net Weight 21.22 lbs
Order Code US and Canada:XT6HU3800BFF000XXX
EAN:8015644033644
Dimensions
Product Net Width:
210 mm
Product Net Height:
268 mm
Product Net Depth / Length:
103.5 mm
Product Net Weight:
9.144 kg
Container Information
Package Level 1 Units:
box 1 piece
Package Level 1 Width:
305 mm
Package Level 1 Height:
285 mm
Package Level 1 Depth / Length:
370 mm
Package Level 1 Gross Weight:
9.625 kg
Package Level 1 EAN:
8015644033644
Additional Information
Circuit Breaker Type to be Associated:
Power Distribution
Product Main Type:
SACE Tmax XT
Product Name:
Moulded Case Circuit Breaker
Product Type:
Automatic Circuit Breaker
Suitable for Product Class:
SACE Tmax XT
Version:
F
CAD Dimensional Drawing:
XT6 3p Fixed Circuit Breaker
XT6 Frontal plate
Technical
Current Type:
AC/DC
Mechanical Durability:
20000 cycle
120 cycles per hour
Number of Poles:
3P
Order Multiple:
1 piece
Power Loss:
at Rated Operating Conditions per Pole 54 W
Rated Current (In):
800 A
Rated Instantaneous Short-Circuit Current Setting (Ii):
4000…8000 A
Rated Operational Voltage:
600 V AC
Rated Ultimate Short-Circuit Breaking Capacity (Icu):
(220 V AC) 100 kA
(230 V AC) 100 kA
(240 V AC) 100 kA
(380 V AC) 70 kA
(415 V AC) 70 kA
(440 V AC) 50 kA
(500 V AC) 50 kA
(525 V AC) 50 kA
(690 V AC) 25 kA
(250 V DC) 2 Poles in Series 70 kA
(500 V DC) 2 Poles in Series 50 kA
(750 V DC) 3 Poles in Series 36 k