Active > Power Components >
Power Supplies
Camtec CPS-EC1500 Battery Charger & Industrial Precision Power Supply
Quick Overview
CAMTEC – 1500W Precision DC Rectifier, DIN-Rail Battery Charger
Camtec CPS-EC1500 1500W Precision DC Rectifier DIN-Rail Battery Charger offers A/V adjustable industrial power with real-time output current monitoring and precision potentiometers for voltage and current adjustment. It features a Power Good Relay for AC and DC status indication, a constant voltage (C/V) curve down to 0V with no foldback, and sense control at 2V per load line. Additionally, it includes an electronic inrush current limiter with a peak of 20.7A, an inhibit function (interlock), external shutdown capability, and a boost charge mode for enhanced performance.
At Camtec, you’ll find a variety of single output DC power supplies designed to ensure reliable and accurate electronic measurements. Whether you need to perform quick checks or detailed assessments, high-quality Camtec equipment provides the confidence you need. Explore Camtec’s extensive selection of bench single output DC power supplies to find the ideal configuration for your specific applications.
Details
CAMTEC – CPS-EC1500 SERIES
1500W Precision DC Rectifier DIN-Rail Battery Charger, C/V Adjustable Industrial Power
Available Outputs: 24V, 36V, 48V, 60V, 72V, 110V, 150V, 220V, 300Vdc
Description The Camtec CPS-EC series is a high precision switch mode power supply for an upscale demand. The unit is C/V adjustable. It is engineered and manufactured by CAMTEC in Germany. The designed meets challenging applications like railway, complex drives, battery charging for DC-UPS, test-stands, machine-building and professional LED lighting. The power supply provides a low ripple-noise, a precise load-regulation and high efficiency up to 92%. High-end long life capacitors guarantee an extended hold-up-time and an extraordinary lifetime of the power supply. The circuit design starts complex loads easily. The internal control circuit manages illegal operating conditions to prevent your system from damages. The CPS-EC series features active high input transients with suppressor diodes, X2-capacitors and varistors. All inputs, outputs and feature connections are galvanic isolated. The design rules set value on extended interference immunity and safety. The unit is designed in accordance to the EN60950-1 and the EMC-compatibility to EN55022 class B norms. Our engineering design is made in accordance to the CSA/UL60950-1 and the IEEE CB scheme rules.
FEATURES
- 1500W Precision DC Rectifier
- DIN-Rail Battery Charger
- C/V Adjustable Industrial Power
- Real time output current monitoring
- Precision potentiometer f. voltage & current
- Power Good Relay AC & DC-ok
- Electronic inrush current limiter 20.7Apeak
- Inhibit function (Interlock). External shutdown
- Precise dynamic response to load change
- Designed for long life under full stress
- Strong input filters. Soft start & auto-recovery
- High reliability. Shock & vibration proof
- EMC meets CE norm class B
- Overload and short circuit protection
Voltage Setting Potentiometer The output voltage limit can be adjusted with a 15 turn high precision potentiometer. The listed values are guaranteed by the factory. The tolerance of the upper margin is -0/+5%. The tolerance of the lower margin is -5%/+0%. The output voltages cover the typical cell voltage range of standard lead acid batteries.
Current Setting Potentiometer The output current limit can be adjusted with a 15 turn high precision potentiometer. The listed values are guaranteed by the factory. The tolerance of the upper margin is -0/+5%. The tolerance of the lower margin is -5%/+0%.
Sensing The device has a sense operation mode to compensate a voltage drop at the load line.
Inhibit contact (Interlock) The inhibit inputs can be connected to a safety contact or a safety relay. When the contact is open the power supply will remain in a completely locked shut down mode. The unit powers up as soon as the contact is closed.
External Shutdown feature All CPS-EC units are featured with a shutdown (open collector).
DC-ok Power Good Relay The PG Relay connection indicates over temperature, low DC-voltage at the output, low AC supply voltage at the input, the inhibit and the shutdown mode.
Galvanic Isolation The power supply is galvanic isolated between the input and the output. All features like Shut Down, Inhibit, Power Good Relay, Sensing and the Current Monitoring are connected to the DC power outputs.
Thermal shutdown The CPS-EC series is featured with a thermal overload shut down and auto recovery behaviour.
GENERAL | |||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Output Voltage | See selection table | ||||||||||||||||||||||||||||||||||||||||||||||||
AC Input Voltage |
184 – 265Vac |
||||||||||||||||||||||||||||||||||||||||||||||||
Frequency | 47-63Hz | ||||||||||||||||||||||||||||||||||||||||||||||||
DC Input Voltage |
250Vdc – 375Vdc |
||||||||||||||||||||||||||||||||||||||||||||||||
AC Input Rating |
230Vac <13,5A |
||||||||||||||||||||||||||||||||||||||||||||||||
DC Input Rating |
250Vdc<7,5A 375Vdc<5,0A |
||||||||||||||||||||||||||||||||||||||||||||||||
Power |
1500W continuous |
||||||||||||||||||||||||||||||||||||||||||||||||
Potentiometer C/V Setting |
15 turn high precision, protective forced isolation to the inputs and the output 3000Vac |
||||||||||||||||||||||||||||||||||||||||||||||||
Operation Failure Relay |
Yes, break contact, protective forced isolation to the inputs and the output 3000Vac |
||||||||||||||||||||||||||||||||||||||||||||||||
Sense Function |
Compensation 2V per load line |
||||||||||||||||||||||||||||||||||||||||||||||||
Remote Shutdown |
Yes, protective forced isolation to the inputs and the output 3000Vac |
||||||||||||||||||||||||||||||||||||||||||||||||
Inhibit Function (Interlock) |
Yes, protective forced isolation to the inputs and the output 3000Vac |
||||||||||||||||||||||||||||||||||||||||||||||||
Derating |
+60°C…+70°C 2.5%/°C |
||||||||||||||||||||||||||||||||||||||||||||||||
Accuracy |
+60°C…+70°C 2.5%/°C |
||||||||||||||||||||||||||||||||||||||||||||||||
Load Regulation |
< ± 0.05% 0-100% |
||||||||||||||||||||||||||||||||||||||||||||||||
Start up from Shutdown |
Typical 420ms |
||||||||||||||||||||||||||||||||||||||||||||||||
Start up from Inhibit |
Typical 420ms |
||||||||||||||||||||||||||||||||||||||||||||||||
Response to Load Change |
<1ms 10-100%, 100-10% |
||||||||||||||||||||||||||||||||||||||||||||||||
Base Load |
None required (open circuit proof) |
||||||||||||||||||||||||||||||||||||||||||||||||
Efficiency 230Vac |
92-94% at 90% load |
||||||||||||||||||||||||||||||||||||||||||||||||
Short Circuit Protection |
Continuous |
||||||||||||||||||||||||||||||||||||||||||||||||
Open Circuit Proof |
Continuous |
||||||||||||||||||||||||||||||||||||||||||||||||
Temperature Control |
Yes, thermal shutdown with auto recovery (+70°C, metering distance 10mm) |
||||||||||||||||||||||||||||||||||||||||||||||||
Hold Up Time |
>20ms 230Vac |
||||||||||||||||||||||||||||||||||||||||||||||||
Inrush Current ±5% |
<14,7Aeff <20,7Apeak (230Vac) active inrush current limiter |
||||||||||||||||||||||||||||||||||||||||||||||||
MCB (Circuit Breaker) |
16A type-B |
||||||||||||||||||||||||||||||||||||||||||||||||
Soft Start |
100ms typical |
RELIABILITY | |||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Isolation Paths |
> 8mm creepage distance & clearance paths |
||||||||||||||||||||||||||||||||||||||||||||||||
Input to Output Isolation |
3000Vac |
||||||||||||||||||||||||||||||||||||||||||||||||
Input to Case Isolation |
2500Vac |
||||||||||||||||||||||||||||||||||||||||||||||||
Output to Case |
500Vdc , models ≥60Vdc 2400Vdc |
||||||||||||||||||||||||||||||||||||||||||||||||
MTBF |
400.000h (IEC61709) |
||||||||||||||||||||||||||||||||||||||||||||||||
MTTF |
144.006h (IEC61709) |
||||||||||||||||||||||||||||||||||||||||||||||||
ROHS |
2011/65/EG confirmed |
||||||||||||||||||||||||||||||||||||||||||||||||
REACH |
EG No. 1907/2006 confirmed |
ENVIRONMENTAL | |||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Cooling |
Controlled and stepless fans from manufacturer EBM Papst (Germany) |
||||||||||||||||||||||||||||||||||||||||||||||||
Ambient Operating Temp. |
– 25°C…+70°C |
||||||||||||||||||||||||||||||||||||||||||||||||
Ambient Storage Temp. |
– 40°C…+85°C |
||||||||||||||||||||||||||||||||||||||||||||||||
Environment . |
Humidity 95% non-condensing @ 25°C, climate class. 3k3, pollution rate II |
STANDARDS AND APPROVALS | |||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
EMI |
EN55022 conducted class B, radiated class A |
||||||||||||||||||||||||||||||||||||||||||||||||
EMS |
EN61000-6-2,3 |
||||||||||||||||||||||||||||||||||||||||||||||||
Safety |
EN60950-1, EN60204-1 |
||||||||||||||||||||||||||||||||||||||||||||||||
Safety Class 1(A) |
VDE0805, VDE0100 |
MECHANICAL | |||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Dimensions (HxWxD) |
161x250x124mm |
||||||||||||||||||||||||||||||||||||||||||||||||
Weight |
4100g |
||||||||||||||||||||||||||||||||||||||||||||||||
AC Terminals |
Input Screw Terminal 3x AWG20 – AWG6 / 0,5 – 16mm² (L,N,PE) |
||||||||||||||||||||||||||||||||||||||||||||||||
DC Terminals |
Output Screw Terminal 4x AWG20 – AWG6 / 0,5 – 16mm² (+ + / – – ) |
MODEL | CPS-EC1500.024 | CPS-EC1500.036 | CPS-EC1500.048 | CPS-EC1500.060 | CPS-EC1500.072 |
---|---|---|---|---|---|
Rated DC Voltage | 24Vdc | 36Vdc | 48Vdc | 60Vdc | 72Vdc |
Rated DC Current | 42A | 28A | 21A | 16,7A | 13,9A |
DC Voltage Setting Range |
24–30V | 36–45V | 48–58V | 60–75V | 72–90V |
DC Current Setting Range |
31,3 – 62,5 | 20,9 – 41,7A | 15,6 – 31,2A | 12,5 – 25,0A | 10,4 – 20,8A |
Overvoltage Protection |
34Vdc | 50Vdc | 67Vdc | 84Vdc | 100Vdc |
Ripple Peak 230Vac 20MHz |
40mV | 40mV | 100mV | 150mV | 200mV |
MODEL | CPS-EC1500.110 | CPS-EC1500.150 | CPS-EC1500.220 | CPS-EC1500.300 |
---|---|---|---|---|
Rated DC Voltage | 110Vdc | 150Vdc | 220Vdc | 300Vdc |
Rated DC Current | 9,1A | 6,7A | 4,55A | 3,33A |
DC Voltage Setting Range |
110 – 137,5Vdc | 132 – 180Vdc | 220 – 264Vdc | 264 – 360Vdc |
DC Current Setting Range |
6,8 – 13,6A | 5,0 – 10,0A |
3,4 – 6,8A |
2,3 – 4,6A |
Overvoltage Protection |
154Vdc | 210Vdc | 310Vdc | 420Vdc |
Ripple Peak 230Vac 20MHz |
300mV | 400mV | 400mV | 400mV |
Optional Coating (option C): We offer the CPS-EC series with an optional coating. It is to be used in e.g. dusty, dirty, high humidity area or in awaiting quick temperature changes. Short circuit and corrosion at print board lines and at solder points can be prevented. The coat itself is a transparent acrylic resin. Peters SL 1306 N-FLZ (transparent) IEC60216-1 2001, IPC-CC-830B, UL listed as permanent coating FileNo.: E80315 , UL94V-0 eg CPS-EC1500.048C