Description
3VA61106JQ310AA0 Siemens (3VA6110-6JQ31-0AA0) circuit breaker 3VA6 UL Frame 150 breaking capacity class H 65 kA @ 480 V 3- pole, line protection ETU560, LSIG, In=100 A overload protection Ir=40 A…100 A short-circuit protection Isd=0.6..10x In, Ii=1.5..12x In neutral conductor protection optionally with external current transformer, up to 160% ground-fault protection Ig=0.2…1 x In, tg=0.05-0.8s without connection.
The Siemens 3VA6110-6JQ31-0AA0 is a 3 Pole solid state molded case circuit breaker with a current rating of 100 Amps and a voltage rating of 600V. It has an interrupting rating of 22kAIC at 600V, 65kAIC at 480V. The 3VA6110-6JQ31-0AA0 features with 3VA61 frame type and includes LSIG – long-time, short-time, instantaneous and ground fault functions.
Specifications
Brand Siemens
Series 3VA
Amperage 100
Voltage 600V
Poles 3
Phase 3
Approval UL
Interrupting Rating 22kAIC at 600V, 65kAIC at 480V
Frame Type 3VA61
Connection Type Feed-Thru
Protection Solid State
Functions LSIG – Long-Time, Short-Time, Instantaneous and Ground Fault
Standards RoHS
Model
product brand name SENTRON
product designation Molded-case circuit breaker
product designation / according to UL file HDAE
design of the product System protection
design of the load switch / according to UL 489 / Heating, Air
Conditioning, and Refrigeration circuit breaker (HACR Type)
Yes
design of the overcurrent release ETU560
protection function of the overcurrent release LSIG
number of poles 3
General technical data
insulation voltage / rated value 800 V
operating voltage / at AC / rated value 690 V
power loss [W] / maximum 13 W
power loss [W] / for rated value of the current / at AC / in hot
operating state / per pole
4.33 W
mechanical service life (operating cycles) / typical 25 000
electrical endurance (operating cycles) / at AC-1 / at 380/415 V 14 000
electrical endurance (operating cycles) / at AC-1 / at 690 V 9 800
electrical endurance (operating cycles) / at 480 V 14 000
electrical endurance (operating cycles) / at 600 V 9 800
product feature / for neutral conductors / upgradable/retrofittable
/ short-circuit and overload proof
Yes
ground-fault monitoring version Summation current formation L-conductor
product function
● communication function Yes
● other measurement function No
Net Weight 2.092 kg
Current
marking / according to UL 489 / 100%-rated breaker No
operational current
● at 40 °C 100 A
● at 45 °C 100 A
● at 50 °C 100 A
● at 55 °C 100 A
● at 60 °C 100 A
● at 65 °C 100 A
● at 70 °C 100 A
Switching capacity according to IEC 60947
switching capacity class of the circuit breaker H
maximum short-circuit current breaking capacity (Icu)
● at 240 V 110 kA
● at 415 V 85 kA
● at 690 V 2.5 kA
operating short-circuit current breaking capacity (Ics)
● at 240 V 110 kA
● at 415 V 85 kA
● at 690 V 2.5 kA
short-circuit current making capacity (Icm)
● at 240 V 242 kA
● at 415 V 187 kA
● at 690 V 3.8 kA
Switching capacity according to UL 489
current breaking capacity
● at 240 V 100 kA
● at 480 V 65 kA
● at 600 V 22 kA
Adjustable parameters
adjustable response value setting current (Ir) / of the L-trip / with
I2t characteristic
● minimum 40 A
● maximum 100 A
adjustable response value delay time (tr) / for L-tripping / with I2t
characteristic
● minimum 0.5 s
● maximum 25 s
adjustable response value setting current (Isd) / of S-trip / with
I0t characteristic
● minimum 60 A
● maximum 1 000 A
adjustable response value setting current (Isd) / of S-trip / with
I2t characteristic
● minimum 60 A
● maximum 1 000 A
adjustable response value delay time (tsd) / for S-tripping / with
I0t characteristic
● minimum 0.05 s
● maximum 0.5 s
adjustable response value delay time (tsd) / for S-tripping / with
I2t characteristic
● minimum 0.05 s
● maximum 0.5 s
adjustable response value setting current (Ii) / for I-tripping
● minimum 150 A
● maximum 1 200 A
adjustable current response value current / for G-tripping / with
standard characteristic
● initial value 20 A
● full-scale value 100 A
adjustable response value delay time (tg) / for G-tripping / with
I0t characteristic
● minimum 0.05 s
● maximum 0.8 s
adjustable response value setting current (Ig) / for G-tripping /
with I2t characteristic
● minimum 20 A
● maximum 100 A
adjustable response value delay time (tg) / for G-tripping / with
I2t characteristic
● minimum 0.05 s
● maximum 0.8 s
adjustable setting current (InN) / for N-tripping