Description
HDL26090 Schneider – Square D Molded Case Circuit Breaker MCC 600V 90A, Adjustable Trip, 900-4500A 3 Pole, Mounting Plug-On, Thermal Magnetic, Current Limiting Type; 4.09 Inch Width X 3.39 Inch Depth X 6.42 Inch Height Size; 600 Volt Max. AC Voltage Rating; 250 Volt Max. DC Voltage Rating; UL, CSA, CE Approval; 600 Volt AC 50/60 Hertz, 250 Volt DC Voltage Rating
HDL26090 is a Square D 2 pole thermal magnetic circuit breaker rated for 90 amps and 600 volts with unit mounting.
This molded case circuit breaker features a thermal magnetic trip unit with long-time and instantaneous functions, suitable for single-phase applications. It has a high interrupting rating of 25kA at 240VAC, 18kA at 480VAC, 14kA at 600VAC, and 20kA at 250VDC, ensuring reliable protection. The breaker is UL, CE, IEC, and CSA certified and uses feed-thru connection with load and line lugs compatible with AWG 14 to 3/0 aluminum or copper wiring.
Key Specifications
Amperage: 90 Amps
Voltage: 600 Volts AC / 250 Volts DC
Poles: 2
Mounting Type: Unit Mount
Interrupting Rating: 25kA @ 240VAC, 18kA @ 480VAC, 14kA @ 600VAC, 20kA @ 250VDC
Series/Frame: HDL
Trip Unit: Thermal Magnetic with Long-Time and Instantaneous Functions
Connection Type: Feed-Thru with Load and Line Lugs
Certifications: UL, CE, IEC, CSA
Dimensions (HxWxD): 6.4 x 4.09 x 3.39 inches
Wire Gauge: AWG 14 to 3/0 Aluminum/Copper
Current Rating: 90 AMPERE
Number of Poles: 2
Interrupting Rating: 25 KILOAMPERE AT 240 VAC, 18 KILOAMPERE AT 480 VAC STAR/277 VAC OR 480 VAC, 14 KILOAMPERE AT 600 VAC STAR/347 VAC OR 600 VAC (UL/CSA/NOM); 25 KILOAMPERE AT 240 VAC, 18 KILOAMPERE AT 415 VAC (IEC); 20 KILOAMPERE AT 250 VDC
Terminal Type: LINE LUG, LOAD LUG
Size: 2.74 INCH W X 4.36 INCH D X 6.4 INCH H
Approval: UL, CSA
Catalog Number: HDL26090
Brand Name: PowerPact[T]
Model: HD
Type: MOLDED CASE, THERMAL MAGNETIC
Frame Type: H
Voltage Rating: 240/480/600 VAC AT 50/60 HZ, 480 VAC STAR/277 VAC AT 50/60 HZ, 600 VAC STAR/347 VAC AT 50/60 HZ (UL/CSA/NOM); 240/415 VAC AT 50/60 HZ (IEC); 250 VDC
Maximum AC Voltage Rating: 600 V
Maximum DC Voltage Rating: 250 V
CATALOG DESCRIPTION: CIRCUIT BREAKER, POWERPACT H, 90A, 2 POLE, 600VAC, 14KA, LUGS, THERMAL MAGNETIC, 80%
Category: 1 Pole Non-Interchangeable Trip Thermal Magnetic Circuit Breakers
Full Technical Description: Thermal Magnetic, Current Limiting Type; 4.09 Inch Width X 3.39 Inch Depth X 6.42 Inch Height Size; 600 Volt Max. AC Voltage Rating; 250 Volt Max. DC Voltage Rating; UL, CSA, CE Approval; 600 Volt AC 50/60 Hertz, 250 Volt DC Voltage Rating; 14 Kiloamp at 600 Volt AC, 20 Kiloamp at 250 Volt DC Interrupting Rating; 90 Amp Current Rating; 2 Pole(S); Line/Load Lug Terminal Type; H Frame Type; POWERPACT[TM] Brand; Rohs/Reach Compliant; Trip Setting 800 Amp (Hold), 1450 Amp (Trip); Mounting Type Unit; Control Type Toggle; Terminal Wire Size 14 to 3/0 AWG (Copper/Aluminum); Continuous Current Rating 80 Percent; Operation Ambient Air Temperature Rating 28 to 158 Deg F; Application Distribution; Applicable Standard Eac, NOM, IEC, CCC, NEMA, En/Iec 60947-2, Federal Specification W-C-375B/Gen; HD Model
Manufacturer: Square D Co.
Manufacturer Brand: Square D Co.
Product Description: Square D HDL26090 Molded Case Circuit Breaker 600V 90A
Proposition 65 Warning (CA): WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.p65warnings.ca.gov
Sub-Category: Non Interchangeable Trip Breaker