Description
HSD10001.72T Camtec Power Supplies 72V 14A 1000W 3 Phase – DIN-Rail RoHS
^The HSD10001 is a 1000W DIN-Rail Power Supply 3-Phase. Metal housing, -20C…+60C full output power, natural convection, galvanic insulated, continuous short circuit protected, overload and low voltage protected, soft start and auto-recovery, temperature control, electronic Inrush Current Limiter, switching frequency 100 KHz, series and parallel operation, high reliability, shock and vibration resistant. The selection of products includes converters, frames and racks, chassis, rails. The main product of the company is power supplies and converters in a wide range of capacities. Camtec manufactures programmable power supplies for automating production processes. The technique is also used in various research centers and laboratories.
DIN-Rail Power Supply 3phase fix output TS35mm DIN EN 50022
Active Inrush Current Protection
Active PFC
Temperature Control
Clean C/V chart without foldback, ideal for dc drives and dc-UPS
Remote Shutdown
HSD10001
Model | HSD10001 | |||||
Power | 960W-1080W | |||||
Nominal AC Input | 3x 400-500Vac / 3x 400-500Vac (75% power) | |||||
Input Range AC | 3x 340-575Vac / 3x 340-575Vac (75% power) | |||||
Input Range DC | 450-820Vdc | |||||
Hold-Up Time | 12ms | |||||
Inrush Current Protection | 14,2Aeff / 20Apeak active protection ±6% | |||||
Autostart | Soft start | |||||
Output Voltage | 12V | 24V | 36V | 48V | 60V | 72V |
Adjust Range Vout | 10,0-15,0V | 22,5-28,5V | 32,0-43,0V | 43,0-53,0V | 53,0-72,0V | 68,0-86,0V |
Ripple & Noise mVpp | 50mV | 50mV | 80mV | 100mV | 100mV | 150mV |
Nominal Output Current 60°/40°C | 50/55A | 40/44A | 28/31A | 21/23A | 17/18A | 14/15A |
Efficiency | 90% | |||||
Basic load | Idling-proof | |||||
Short Circuit Protection | Continuous | |||||
Cooling | Natural convection | |||||
Dimensions (WxHxD) | 200×131,5×120,8mm | |||||
Safety Standards | EN61010-1, EN6101-2-201, EN62368-1, EN60204-1, EN60950-1 | |||||
Input to Output Isolation | 3000Vac | |||||
EMI | EN55032 class B, EN61000-6-3, EN61000-3-2 | |||||
EMS | EN61000-6-2 | |||||
MTBF | 500.000h | |||||
Power Good Relay | Yes | |||||
Remote Shutdown | Yes |
Manufacturer:Camtec
Datasheet:Camtec/hsd10001.pdf