Description
RGA36120CU31A Schneider Electric Molded Solid State Circuit Breaker PowerPact™ RGA Series, R-Frame, 1200A, 600V ac, 3-Pole, 13.38 H x 14.96 W x 13.78 D in. DIN Rail Lever 3-Poles CSA, UL
PowerPacT R-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT R-Frame circuit breakers have either a fixed long time electronic trip unit, ET 1.0I, or Micrologic trip units. Micrologic trip units can be interchanged in the field to allow for maximum flexibility; the basic electronic trip unit doesn’t have that interchangeability. This circuit breaker has a Micrologic Interchangeable Standard Trip with a 3.0 trip unit and an LI function. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT R circuit breakers are available in 2, 3, and 4-pole unit mount and I-Line construction (I-Line construction is available for 1000A and 1200A rated circuit breakers only). This unit has I-Line terminations on the line side and mechanical lugs on the load side. This PowerPacT P, 1200A, 3 pole, circuit breaker has an interrupting rating of 18kA at 600VAC. This circuit breaker has a continuous current rating of 100% with an ABC phase connection. PowerPacT R circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
Complementary Attributes
ICS Rated Service Breaking Capacity: 25 kA 240 V AC 50/60 Hz IEC 60947-2, 20 kA 380/415 V AC 50/60 Hz IEC 60947-2
UE Rated Operational Voltage: 600 V AC 50/60 Hz UL 489
Used On: CLASS 825/0612 I-LINE[R] PANELBOARD/SWITCHBOARD
Approval: UL, CSA
Additional Information: FRAME TYPE R; MOUNTING TYPE PLUG ON; SIZE 16.54 INCH W X 14.49 INCH D X 16.24 INCH H; TERMINAL WIRE SIZE (4) 3/0 AWG TO 600 KCMIL (ALUMINUM/COPPER)
Catalog Number: RGA36120CU31A
Brand Name: PowerPact[T]
Model: RG
Voltage Rating: 240/480/600 VAC AT 50/60 HZ, 480 VAC STAR/277 VAC, 600 VAC STAR/347 VAC AT 50/60 HZ (UL/CSA/NOM); 240/415 VAC AT 50/60 HZ (IEC)
Current Rating: 1200 AMPERE
Number of Poles: 3
Interrupting Rating: 65 KILOAMPERE AT 240 VAC, 35 KILOAMPERE AT 480 VAC STAR/277 VAC OR 480 VAC, 18 KILOAMPERE AT 600 VAC STAR/347 VAC OR 600 VAC (UL/CSA/NOM); 50 KILOAMPERE AT 240 VAC, 35 KILOAMPERE AT 415 VAC (IEC)
Application: POWER DISTRIBUTION
CATALOG DESCRIPTION: CIRCUIT BREAKER, POWERPACT R, 1200A, 3 POLE, 600VAC, 18KA, I-LINE, MICROLOGIC 3.0, 100%
Category: 3 Pole Non-Interchangeable Trip Electronic Circuit Breakers
Full Technical Description: Electronic, Standard, Micrologic 3.0, LI Type; I-Line Panelboard and Switchboard Used on; UL, CSA Approval; Power Distribution Application; 600 Volt AC 50/60 Hertz Voltage Rating; 18 Kiloamp at 600 Volt AC Interrupting Rating; 1200 Amp Current Rating; 3 Pole(S); POWERPACT[TM] Brand; Rohs/Reach Compliant; Overall Dimension 16.54 Inch Width X 14.49 Inch Depth X 16.24 Inch Height; Frame Type R; Terminal Type I-Line Connection Line Lug Load; Control Type Operating Handle; Terminal Wire Size (4) 3/0 AWG to 600 kcmil (Copper/Aluminum); Continuous Current Rating 100 Percent; Phase Connection Type ABC; Applicable Standard Nmx, IEC; RG Model
Manufacturer: Square D Co.
Breaker Type: Solid State
Mounting Type: DIN Rail
Number of Poles: 3
Illumination: 3
Actuator Type: Lever
VoltageRating: 600V AC
Current Rating: 1.2kA (Amps)
Package: Box