W3G630-NP04-H1 EBM AC Fan 230V 410W Axial

Please call 800-717-6475 to check current stock and pricing.

The ebmpapst W3G630-NP04-H1 Fan: EC; axial; 230VAC; 805x805x255mm; 6785m3/h; ball; 830rpm; IP55

SKU: W3G630-NP04-H1 Category: Brand:

Description

ebm-papst W3G630-NP04-H1 Reliable, industrial fan High Power Cooling AC Fan 410W EC; 230VAC 6785m3/h; ball; 830rpm; IP55 Axial 805x805x255mm

Part # Alias: W3G630NP04H1
Weight 20,4 kg
Motor size 84
Size 630 mm
Rotor surface Painted black
Terminal box material PP plastic
Electronics housing material Die-cast aluminum, painted black
Impeller material PP plastic
Fan housing material Sheet steel, galvanized and coated with black plastic (RAL 9005)
Guard grille material Steel, coated with black plastic (RAL 9005)
Number of blades 5
Blade pitch 0°
Airflow direction V
Direction of rotation Clockwise, viewed toward rotor
Degree of protection IP55
Insulation class “F”
Moisture (F) / Environmental (H) protection class H2
Max. permitted ambient temp. for motor (transport/storage) +80 °C
Min. permitted ambient temp. for motor (transport/storage) -40 °C
Installation position Shaft horizontal or rotor on bottom; rotor on top on request
Condensation drainage holes On rotor side
Mode S1
Motor bearing Ball bearing / (sealed)
Technical features – Output 10 VDC, max. 10 mA – Operation and alarm display – Alarm relay – Integrated PID controller – Power limiter – Motor current limitation – PFC, active – RS-485 MODBUS-RTU – Soft start – Control input 0-10 VDC / PWM – Control interface with SELV potential safely disconnected from the mains – Thermal overload protection for electronics/motor – Line undervoltage / phase failure detection
EMC immunity to interference According to EN 61000-6-2 (industrial environment)
EMC circuit feedback According to EN 61000-3-2/3
EMC interference emission According to EN 61000-6-3 (household environment)
Touch current according to IEC 60990 (measuring circuit Fig. 4, TN system) <= 3,5 mA Electrical hookup Terminal box Motor protection Thermal switch auto reset, internally connected Protection class assignment I; If a protective earth is connected.|The built-in component has several local protection class assignments.|The final protection class is determined by the intended installation. Conformity with standards EN 61800-5-1 / CE Approval UL 1004-7 + 60730-1 / EAC / CSA C22.2 No. 77 + CAN/CSA-E60730-1 Nominal data Phase 1~ Type of voltage AC Nominal voltage in V 230 Nominal voltage range in V 200 .. 270 Frequency in Hz 50/60 Type of data definition maximum load Speed in min-1 830 Power input in W 410 Current draw in A 1,8 Max. back pressure in Pa 100 Max. ambient temperature in °C 60 W3G630NP04H1 Operating instructions

You may also like…