TKMA31200WL GE ABB General Electric Molded Case Circuit Breakers Feed-Thru – 1200 Amp – 3 Pole – 600 V
Designed for standalone enclosure mounting, the GE TKMA31200WL delivers 1200A of thermal-magnetic protection. Unlike standard bolt-on models, this unit-mount (feed-thru) K-frame breaker comes equipped with line and load lugs (TCAL121) for flexible installation in switchboards and motor control centers. It features an interchangeable trip unit with long-time and instantaneous (LI) functions. Rated at 42kAIC at 240VAC, it provides robust overcurrent defense for demanding industrial applications.
TKM Frame Style, Molded Case Circuit Breaker, Thermal Magnetic Interchangeable Trip Unit, 1200 Ampere at 40 Degree Celsius, 3 Pole, 600VAC @ 50/60HZ, Interrupting Ratings: 42 Kiloampere @ 240V AC, 30 Kiloampere @ 480V AC, 22 Kiloampere @ 600V AC, 20 Kiloampere @ 250V DC, Line and Load End Terminals Standard.
This product image represents a base model and is for identification purposes only. Are you purchasing accessories and your breaker in the same order? We will install your accessories to meet your specific configuration needs at NO ADDITIONAL COST! Just provide the necessary information in the order comment box during checkout.
Specifications
Manufacturer General Electric GE
Warranty One Year
Connection Bolt On
Frame Type K
Amperage 1200
Poles 3
Voltage Max 600
Interrupting Capacity Rating 42 Kiloampere @ 240V AC, 30 Kiloampere @ 480V AC, 22 Kiloampere @ 600V AC, 20 Kiloampere @ 250V DC
Trip Setting 3600-10000
Standard Lug Type Line and Load